Water main under the river Schelde

· Water main, Utility, Water, Antwerp, Belgium

Rehabilitation in the port of Antwerp

Situation

One of the most important culverts, running approximately 17 m under the river Schelde in the port of Antwerp, had several leakages due to faulty connections of the pipe. The culvert is installed in a concrete siphon with a diameter of 3 m. To maintain the water supply to the industrial estates in the port and because of the limited accessibility to the pipeline, the client decided to renovate the main with a trenchless method.

Special features

Removal of welding seams

Prior to Primus Line® installation, the host pipe was CCTV-inspected two times to make sure that there were no welding seams.

Debris removal

To remove the debris out of the pipe after cleaning, a gap between two pipe shots had been created at the low point of the pipe.

Technical details

Material of host pipe

Butt-welded steel

Diameter of host pipe

DN 600

Transported fluid

Potable water

Operating pressure

6 bar

Total length

225 m

Number of sections

1 section

Number of bends

6 bends of 45° and 90°

Installation time

5 working days

Why Primus Line?

Ability to negotiate bends

Minimal space requirements